Particularly recommended for use in environmentally sensitive applications or where a high level of fire safety is required, NYCODIEL 1258 combines improved heat resistance, fire safety, and low temperature capability. Its excellent environmental profile makes it an ideal the replacement to mineral and silicone oils.
- 01 Excellent oxidation stability (IEC 61125 method C)
- 02 Meets IEC 61039 K3 fire safety class requirements
- 03 Biodegradability 84% (OECD 301B)
- 04 Not hazardous for the environment
- 05 MR VCUTAP®, DEETAP®, and COMTAP® tap-chargers approved
More information
With extra low pour point and low viscosity at low temperature, NYCODIEL® 1258 might be used at temperatures as low as -40°C.
With high saturation limits, NYCODIEL® 1258 can absorb large quantities of moisture without impacting breakdown voltage. It enables slower ageing of transformers, extension of cellulose insulation life, reduction of bubble evolution during overloads and of condensation during cool down.
NYCODIEL 1258 are fully compatible and miscible in all proportions with mineral oil, natural ester oils and other synthetic esters meeting the same specification but are not miscible with silicone oils.
Properties | Unit | Typical result | IEC 61099 | Test method |
---|---|---|---|---|
Appearance | Limpid | Limpid | Visual examination | |
Colour Alpha | 50 | max 200 | ISO 22111 | |
Density at 20°C | kg/dm3 | 0.97 | max 1 | ISO 12185 |
Kinematic viscosity at 100°C 40°C -20°C -30°C -40°C |
mm2/s | 5.2 27.2 1150 3350 12200 |
- max 35 max 3000 - - |
ISO 3104 |
Pour Point | °C | -60 | max -45 | ISO 3016 |
Flash Point PM | °C | 255 | min 250 | ISO 2719 |
Flash Point COC | °C | 266 | ISO 2592 | |
Fire Point | °C | 310 | min 300 | ISO 2592 |
Inferior Heating Power | MJ/kg | 31.8 | ASTM D240 | |
Water Content | mg/kg | 30 | max 200 | IEC 60814 |
Acid Value | mg KOH/g | 0.01 | max 0.03 | IEC 2021-2 |
Oxidation Stability Total Acid Total Deposit |
mg KOH/g % |
0.04 0.002 |
max 0.3 max 0.01 |
IEC 61125 method C |
Breaking Voltage | kV | 80 | min 45 | IEC 60156 |
Dielectric Dissipation Factor 90°C and 50Hz | 0.01 | max 0.03 | IEC 60247 | |
DC resistivity at 90°C | GΩ.m | >50 | min 2 | IEC 60247 |
Thermal expansion coefficient | °C-1 | 8.3 10-4 | ||
Heat Capacity at 20°C 90°C |
J/kg.K | 1843 1983 |
||
Thermal Conductivity at 24°C 92°C |
W/m.K | 0.14 0.13 |
||
Biodegradability, 28 days | % | 84 | OECD 301B |